Wire cross-section sizing.

Estimate a copper conductor size from load current or active power, cable length and voltage drop. Read the result together with its installation assumptions.

Input guide & diagram
One-way length Lmm²

Copper/PVC/B2 reference, 30°C ambient. Conservative three-loaded-core ampacity. Set the correction factor for actual conditions. Power means active electrical input in W/kW; three-phase uses total power and line-to-line voltage.

Explore unit converters →
WIRE CROSS-SECTION SIZING

Need help? Select ? beside an input.

?

Single-phase AC is common for household appliances; DC is used by batteries. Use three-phase only for a balanced three-phase load.

?

Use the supply voltage from the equipment or circuit. For three-phase calculations enter line-to-line voltage, not phase-to-neutral voltage.

?

Use operating current from the equipment label or a measurement. A is amperes, not power in watts.

?

Enter one-way length from the source to the load. Do not double it for the return wire; the formula accounts for that.

?

Power factor is a decimal from greater than 0 up to 1, such as 0.9. Use the equipment value. A simple resistive load is near 1; do not assume the example fits every appliance. DC ignores this value.

?

The maximum voltage loss you allow along the cable, as a percent of supply voltage. 3% is the example, not a universal requirement.

Reduces cable current capacity for higher temperatures or grouped cables. 1 means reference conditions; 0.8 means 80% of the reference capacity. Enter a value greater than 0 and at most 1.

How to choose this factor

This tool uses copper/PVC cable in conduit on a wall (B2), 30°C ambient, with a 70°C conductor limit. Use 1 only when no temperature or grouping reduction is needed for those reference conditions.

PVC temperature factor (cables in air)
AmbientFactor
30°C1.00
35°C0.94
40°C0.87
45°C0.79
50°C0.71

If cables are grouped, multiply the applicable temperature and grouping factors: k = k temperature × k grouping. At 40°C, 0.87 is the temperature factor only; apply any grouping reduction as well.

For example, a reference capacity of 27 A with k = 0.8 becomes 21.6 A. Lower factors may require a larger conductor.

Select grouping factors from the cable manufacturer's data or the applicable installation standard for the actual spacing, arrangement and number of loaded circuits. These temperature values do not apply to buried cables, XLPE insulation or other installation methods.

Schneider Electric: correction-factor tables ↗

Use a decimal point, for example 12.5.

Preliminary conductor cross-section
4mm²

Load current: 20 A

Voltage drop: 6.44084542986 V

Voltage drop percentage: 2.8003675782 %

Corrected current capacity: 27 A

This is a preliminary size for the stated cable conditions. Protection and installation checks are separate.

Try an example
Formula and assumptions
ΔV = kIL(R cosφ + X sinφ); choose Iz × correction ≥ load current

Preliminary copper/PVC sizing for B2: multicore cable in conduit on a wall, 30°C ambient, 70°C conductor. Three-loaded-core ampacity is used conservatively for all supply modes.

Power input is active electrical input power, total for all phases: DC I = P/V; single-phase I = P/(V × PF); balanced three-phase I = P/(√3 × VLL × PF). Motor mechanical output must first be converted to electrical input using efficiency.

One-way cable length. Balanced sinusoidal three-phase uses line-to-line voltage and line current; AC power factor is lagging cosφ. DC uses two conductors.

Conservative resistance 23.7/S Ω/km and reactance 0.08 Ω/km. Apply a combined correction factor for actual temperature/grouping; 1 is only the reference condition.

Checks steady-state voltage drop and load ≤ corrected ampacity only. Circuit-breaker selection and coordination with the cable are separate checks. Short-circuit withstand, trip/disconnection times, neutral/PE sizing, harmonics, motor starting and local code compliance still require verification.

Inputs are converted to base units before calculation. Display uses 12 significant digits; accuracy depends on measurements and assumptions.

Practical guide
TRY THE NUMBERS

Practical examples

Worked example

Single-phase 230 V, 20 A, one-way length 30 m, power factor 0.9, maximum drop 3% and correction 1 give 4 mm² in this model. Drop is about 2.80%; corrected capacity is 27 A.

READ THE RESULT

How to read the result

  • The result is conductor cross-section in mm², not cable diameter in mm. The model checks both voltage drop and corrected current capacity.
  • Use the actual cable route length in one direction. For power input, enter active electrical input power; three-phase means total power for a balanced load.
  • This is a preliminary copper/PVC/B2 model. Confirm the cable, installation method, protection, starting current and local requirements before selecting equipment.

Frequently asked questions

What does correction factor 0.8 mean?

A reference capacity of 27 A becomes 27 × 0.8 = 21.6 A. The factor reduces capacity, not load current. Choose it for actual temperature and cable grouping.

Should I double the cable length?

No. Enter one-way length. The model accounts for the return path for DC/single-phase and uses the three-phase relationship where applicable.

Can this result choose my circuit breaker?

No. This tool does not select a breaker or verify short-circuit and protective-device coordination. The default 3% drop is a calculation target, not a universal requirement.

UNITNEX

Calculation report

Use your browser's print destination to print or save as PDF.

Install UnitNex

Unit converters and calculators in a dedicated app window.

Choose the install icon in Chrome’s address bar or the install option in its menu. On iPhone or iPad, open UnitNex in Safari and choose Share → Add to Home Screen.

Calculations need an internet connection.