Practical examples
Worked example
Single-phase 230 V, 20 A, one-way length 30 m, power factor 0.9, maximum drop 3% and correction 1 give 4 mm² in this model. Drop is about 2.80%; corrected capacity is 27 A.
Estimate a copper conductor size from load current or active power, cable length and voltage drop. Read the result together with its installation assumptions.
Copper/PVC/B2 reference, 30°C ambient. Conservative three-loaded-core ampacity. Set the correction factor for actual conditions. Power means active electrical input in W/kW; three-phase uses total power and line-to-line voltage.
Preliminary copper/PVC sizing for B2: multicore cable in conduit on a wall, 30°C ambient, 70°C conductor. Three-loaded-core ampacity is used conservatively for all supply modes.
Power input is active electrical input power, total for all phases: DC I = P/V; single-phase I = P/(V × PF); balanced three-phase I = P/(√3 × VLL × PF). Motor mechanical output must first be converted to electrical input using efficiency.
One-way cable length. Balanced sinusoidal three-phase uses line-to-line voltage and line current; AC power factor is lagging cosφ. DC uses two conductors.
Conservative resistance 23.7/S Ω/km and reactance 0.08 Ω/km. Apply a combined correction factor for actual temperature/grouping; 1 is only the reference condition.
Checks steady-state voltage drop and load ≤ corrected ampacity only. Circuit-breaker selection and coordination with the cable are separate checks. Short-circuit withstand, trip/disconnection times, neutral/PE sizing, harmonics, motor starting and local code compliance still require verification.
Inputs are converted to base units before calculation. Display uses 12 significant digits; accuracy depends on measurements and assumptions.
Single-phase 230 V, 20 A, one-way length 30 m, power factor 0.9, maximum drop 3% and correction 1 give 4 mm² in this model. Drop is about 2.80%; corrected capacity is 27 A.
A reference capacity of 27 A becomes 27 × 0.8 = 21.6 A. The factor reduces capacity, not load current. Choose it for actual temperature and cable grouping.
No. Enter one-way length. The model accounts for the return path for DC/single-phase and uses the three-phase relationship where applicable.
No. This tool does not select a breaker or verify short-circuit and protective-device coordination. The default 3% drop is a calculation target, not a universal requirement.