Calculate airflow from air speed and the internal size of a round or rectangular duct. Use the result to compare a measured flow with a planned flow.

Input guide & diagram
Inside dimensions: diameter for a round duct, width and height for a rectangular duct diameterwidthheight

Use clear inside dimensions and average velocity. Nominal DN/NPS is not inside diameter.

Explore unit converters →
AIRFLOW

Need help? Select ? beside an input.

?

Use average speed across the full pipe or duct, not a peak reading at one point. For duct sizing this is your chosen target speed.

?

Use the clear inside width. Room dimensions use the same unit for length, width and height.

?

Use the clear inside height. Room dimensions use the same unit for length, width and height.

?

Measure the inside diameter. A nominal pipe size such as DN50 is not necessarily a 50 mm inside diameter.

Use a decimal point, for example 12.5.

Volumetric airflow
1,800m³/h

Cross-sectional area: 0.1 m²

This is the volume of air passing each unit of time, assuming the entered speed is an average across the duct.

Try an example
Formula and assumptions
Q = v × A; circle A = πd²/4; rectangle A = w × h

Steady volumetric airflow and average velocity at the same gas conditions.

Use internal duct dimensions. Calculated duct sizes are theoretical, not rounded to manufactured sizes.

This does not calculate pressure loss, fan selection, mixing efficiency or ventilation compliance.

Inputs are converted to base units before calculation. Display uses 12 significant digits; accuracy depends on measurements and assumptions. Circular geometry uses an approximate value of π.

Practical guide
TRY THE NUMBERS

Practical examples

Worked example

A 400 × 250 mm duct has area 0.1 m². At average velocity 5 m/s, flow is 0.5 m³/s, or 1800 m³/h.

READ THE RESULT

How to read the result

  • Measure the clear internal dimensions, not the outside size or insulation.
  • Use average velocity across the duct; one point near the wall may not represent it.
  • The result is volume per time, not air pressure or fan power.

Frequently asked questions

Can I use a single anemometer reading?

Only if it represents the section average. Uneven flow can require measurements at several points.

Does this select a fan?

No. Fan selection also needs system resistance and a fan performance curve.