Practical examples
Worked example
A 400 × 250 mm duct has area 0.1 m². At average velocity 5 m/s, flow is 0.5 m³/s, or 1800 m³/h.
Calculate airflow from air speed and the internal size of a round or rectangular duct. Use the result to compare a measured flow with a planned flow.
Use clear inside dimensions and average velocity. Nominal DN/NPS is not inside diameter.
Steady volumetric airflow and average velocity at the same gas conditions.
Use internal duct dimensions. Calculated duct sizes are theoretical, not rounded to manufactured sizes.
This does not calculate pressure loss, fan selection, mixing efficiency or ventilation compliance.
Inputs are converted to base units before calculation. Display uses 12 significant digits; accuracy depends on measurements and assumptions. Circular geometry uses an approximate value of π.
A 400 × 250 mm duct has area 0.1 m². At average velocity 5 m/s, flow is 0.5 m³/s, or 1800 m³/h.
Only if it represents the section average. Uneven flow can require measurements at several points.
No. Fan selection also needs system resistance and a fan performance curve.